@ARTICLE{Saha_Arindita_Analysis_2023, author={Saha, Arindita and Chiranjeevi, Tirumalasetty and Devarapalli, Ramesh and Babu, Naladi Ram and Dash, Puja and Garcìa Màrquez, Fausto Pedro}, volume={vol. 33}, number={No 4}, journal={Archives of Control Sciences}, pages={861-884}, howpublished={online}, year={2023}, publisher={Committee of Automatic Control and Robotics PAS}, abstract={The current task explores automatic generation control knowledge under old-style circumstances for a triple-arena scheme. Sources in area-1 are thermal-solar thermal (ST); thermalgeothermal power plant (GPP) in area-2 and thermal-hydro in area-3. An original endeavour has been set out to execute a new performance index named hybrid peak area integral squared error (HPA-ISE) and two-stage controller with amalgamation of proportional-integral and fractional order proportional-derivative, hence named as PI(FOPD). The performance of PI(FOPD) has been compared with varied controllers like proportional-integral (PI), proportional-integralderivative (PID). Various investigation express excellency of PI(FOPD) controller over other controller from outlook regarding lessened level of peak anomalies and time duration for settling. Thus, PI(FOPD) controller’s excellent performance is stated when comparison is undergone for a three-area basic thermal system. The above said controller’s gains and related parameters are developed by the aid of Artificial Rabbit Optimization (ARO). Also, studies with HPA-ISE enhances system dynamics over ISE. Moreover, a study on various area capacity ratios (ACR) suggests that high ACR shows better dynamics. The basic thermal system is united with renewable sources ST in area-1 also GPP in area-2. Also, hydro unit is installed in area-3. The performance of this new combination of system is compared with the basic thermal system using PI(FOPD) controller. It is detected that dynamic presentation of new system is improved. Action in existence of redox flow battery is also examined which provides with noteworthy outcome. PI(FOPD) parameters values at nominal condition are appropriate for higher value of disturbance without need for optimization.}, type={Article}, title={Analysis of multiple-area renewable integrated hydro-thermal system considering artificial rabbit optimized PI (FOPD) cascade controller and redox flow battery}, URL={http://ochroma.man.poznan.pl/Content/130021/art08_int.pdf}, doi={10.24425/acs.2023.148885}, keywords={solar thermal, automatic generation control, geothermal, artificial rabbit optimization, redox flow battery, PI(FOPD) controller}, }