@ARTICLE{Chen_Xiao-Qiang_Thirty-six_2016, author={Chen, Xiao-Qiang and Hao, Chun-Ling and Qiu Hao and Li Min}, volume={vol. 65}, number={No 1 March}, journal={Archives of Electrical Engineering}, pages={117-132}, howpublished={online}, year={2016}, publisher={Polish Academy of Sciences}, abstract={In this paper, a low kilo-volt-ampere rating zigzag connected autotransformer based 36-pulse rectifier system supplying vector controlled induction motor drives (VCIMD) is designed, modeled and simulated. Detailed design procedure and magnetic rating calculation of the proposed autotransformer and interphase reactor is studied. Moreover, the design process of the autotransformer is modified to make it suitable for retrofit applications. Simulation results confirm that the proposed 36-pulse rectifier system is able to suppress less than 35th harmonics in the utility line current. The influence of load variation and load character is also studied to demonstrate the performance and effectiveness of the proposed 36-pulse rectifiers. A set of power quality indices at AC mains and DC link are presented to compare the performance of 6-, 24- and 36-pulse AC-DC converters.}, type={Artykuły / Articles}, title={Thirty-six pulse rectifier scheme based on zigzag auto-connected transformer}, URL={http://ochroma.man.poznan.pl/Content/85192/PDF/DOI%2010.1515aee-2016-0009.pdf}, doi={10.1515/aee-2016-0009}, keywords={autotransformer, harmonic suppression, multipulse rectifier, power quality}, }